Products Information and Services
 |
|
High frequency On line |
HP9110/9111 1-3KVA
|
| Applications |
| Servers,Data-Center,Cirtical network devices,Sensitive equip - |
ment,Telecom....
|
| KEY FEATURES |
True on-line double conversion technology with advanced microprpcessor control |
Wide input voltage |
Zero transfer time |
Protection against all types of power problems |
Set test while start of the ups |
Site wiring fault warning |
On-battery power-on function |
HP9110E
 |
Smart RS232 communication interface |
| |
| |
| |
| |
HP9111C |
| |
|
| |
¡¡TECHNICAL SPECIFICATIONS
| Model |
|
HP9110E/9111C 1KT |
HP9110E/9111C 2KT |
HP9110E/9111C 3KT |
HP9110E/9111C 1KT -XL |
HP9110E/9111C 2KT -XL |
HP9110E/9111C 3KT-XL |
| Capacity |
VA/W |
1KVA/0.7KW |
2KVA/1.4KW |
3KVA/2.1KW |
1KVA/0.7KW |
2KVA/1.4KW |
3KVA/2.1KW |
| Input |
Nominal Voltage |
110/115/120VAC or 220/230/240VAC |
| Voltage Range |
180-300VAC |
| Frequency Range |
50Hz;46-54Hz:60Hz:56-64Hz |
| Phase |
Single phase |
| Power Factor |
>0.97 |
| Connection |
IEC320-10A inlet |
IEC320-10A inlet |
IEC320-16A inlet |
IEC320-10A inlet |
IEC320-10A inlet |
IEC320-16A inlet |
| Output |
Voltage |
110/115/120¡Á£¨1¡À2%£©VAC 220/230/240¡Á£¨1¡À2%£©VAC |
| Frequency |
Synchronization range(line mode);50 or 60Hz¡Á£¨1¡À0.2%£©(Battery mode) |
| Phase |
Single phase |
| Wave Form |
Sine Wave |
| Power Factor |
0.7 or 0.8 optional |
| Voltage Distortion |
3% |
4% |
4% |
3% |
4% |
4% |
| Overload Capability |
110%-150% for 30 sec.,¡Ý150% for 200 ms |
| Current Crest Radio |
3£º1 |
| Connections |
IEC320*4 |
IEC320*6 |
IEC320*3&Terminal bolock |
IEC320*4 |
IEC320*6 |
IEC320*3&Terminal bolock |
| Battery&charge |
Type |
Sealed,Maintenance free,Lead-acid |
| Nominal DC to Voltage |
|
|
|
36VDC |
96VDC |
96VDC |
| Quantity |
3 pieces |
8 pieces |
8 pieces |
Depends on the requested back-up time |
| Back-up time(full load) |
5 min |
9 min |
5min |
Depends on the capacity of the external battery bank |
| Recharge Time |
5 hrs to 90% of capacity |
Depends on the capacity of the external battery bank |
| Automatic Transfer |
On overload and UPS failure |
| Before UPS power-on |
Default ''ON' user adjustable to 'YES' |
| Voltage Range |
40-132VAC (Default),user adjustable within 40-143VAC or 80-264VAC (Default),user adjustable within 80-286VAC |
| Transfer time |
AC to DC Zero |
Inverter to Bypass 4 ms (Typical) |
| Indicators |
UG/LED display |
Load level / Battery / lever, Battery, Utility power, Inverter, Bypass,Overload, Fault |
| UX/LCD display |
UPS status, I/P & O/P voltage & frequency, Battery voltage, Battery capacity, Loading, Temperature, History record |
| Audible alarm |
|
Bypass, On battery mode, Battery low, Overload, Fault |
| Acoustic noise |
At 1 meter distance |
£¼45 dB |
£¼50 dB |
£¼50 dB |
£¼45 dB |
£¼50 dB |
£¼50 dB |
| Communications |
DB-9 Port |
PS-232 Serial interface |
| Intelligent Slot |
Options:SNMP Card, AS400 Card or Winpower CMC / (usb port) |
| Environment |
Operating Temperature |
0-40¡æ |
| Operatint Humidity |
20-90% non-condensing |
| Weight |
Net(Kg) |
13 |
31.5 |
32 |
7 |
13.5 |
14 |
| Dimensions(package) |
W ¡ÁD ¡ÁH (mm) |
240¡Á495¡Á335 |
335¡Á590¡Á480 |
355¡Á590¡Á480 |
240¡Á495¡Á335 |
335¡Á590¡Á480 |
335¡Á590¡Á480 |
|
¡¡The series of HP9110E is the UG series before,the series of HP9111C is the UX series before
|
|