- Parameter
SP4U-48100 | ||
System | Cooling method | Fans |
Installation method | 19-inch rack or embedded cabinet mount | |
Incoming way | Front | |
Protection degree | IP20 | |
Maintenance path | Front | |
AC Distribution | Input | 220 Vac single phase |
Inputout voltage | rating voltage:220 Vac 85-290Vac | |
Frequency | 45–65 Hz,Rating Frequency:50/60 Hz | |
Input breaker | 1 ×63A/2P | |
DC Distribution | Output voltage | 42–58 Vdc,rating voltage:53.5 Vdc |
Maximum capacity | 6 kW | |
Battery breaker | 1×100 A/2P | |
Output | 6×16A/1P | |
Rectifier Module | Model | SR4850/SR4850 Plus |
Rated power | 176–290 Vac | |
Dimension (W x D x H) | 85.3 mm × 287 mm × 132.3 mm | |
Efficiency | > 96% | |
Monitoring Module | Model | 2433 |
Communication port | RS232, RS485 | |
Environment | Operating temperature | -5℃ ~ 40℃ |
Storage temperature | -40℃ ~ +70℃ | |
Humidity | ≤90% RH | |
Altitude | ≤2000M |