Double IGBT technical,input PFC>0.99,Thdi<3%;
Efficiency up to 96.5% with three-level technology;
Big charger power reach up to 15% of total power;
Intelligent LCD screen support 12 languages,such as English,Russian.Spanish,French,Korean,Italy,Turkish ;
The internal air channel is designed in such a way that internal hot air drives directly towards the heat sink,without distressing the PCBs and other internal sensitive circuits.
Reliable,efficient,flexible and easy to use
The new generation HP9335 II series is a ups solution designed to meet the needs of SEMS with low investment costs , sustainable operating cost savings,high reliability,and fast and flexible adaptation.
Key Features :
- Parameter
Model | Standard unit | HP9335C Ⅱ 10-40KT | - | |||||||
Long run unit | HP9335C Ⅱ 10-120K XL | |||||||||
Nominal Ratings(kVA) | 10 | 20 | 30 | 40 | 50 | 60 | 80 | 100 | 120 | |
Input | ||||||||||
Nominal input voltage(V) | 380/400/415 | |||||||||
Input voltage range(V) | 228-478 | |||||||||
Nominal input frequency(Hz) | 50/60 | |||||||||
Input frequency range(Hz) | 40-70 | |||||||||
Bypass voltage tolerance(%) | Upper limit: +10%, +15%, or +20% default:+15%; Lower limit: -10%, -20%, -30% or -40% default: -20% | |||||||||
Bypass frequency tolerance(%) | +/- 10% or +/- 20%, default: +/-10% | |||||||||
Input power factor | >0.99 | |||||||||
Current THD at full linear load(THDi%) | <3% | |||||||||
Battery | ||||||||||
Battery voltage | Standard unit | 30pcs 12V 7AH | 30pcs 12V 7AH | 60pcs 12V 7AH | 64pcs 12V 9AH | - | ||||
Long run unit | ±192V~±264Vdc; battery quantity 32-44 pcs (optional) | |||||||||
Temperature compensation (mV/℃/Cell) | -3.0 (selectable from 0 to -5.0 around 25°C or 30°C, or inhibit) | |||||||||
Battery charger current(A) | 0~20( adjustable) | 0~40( adjustable) | ||||||||
Output | ||||||||||
Nominal output voltage(V) | 380/400/415 | |||||||||
Nominal output frequency(Hz) | 50/60 | |||||||||
Output power factor | 1 | 1 | 1 | 1 | 1 | 0.9 | 1 | 1 | 0.9 | |
THDv with 100% linear load(%) | <1% | |||||||||
Inverter overload capacity | 110% for 60 min; 125% 10min; 150% for 1 min; >150% for 200ms | |||||||||
Online mode efficiency | Up to 96.5% | |||||||||
ECO-Mode efficiency | Up to 99.1% | |||||||||
Parallel | Parallel up to 6 units | |||||||||
Dimensions and weight | ||||||||||
Dimensions(W×D×H)mm | Standard unit | 300×700×1105 | 300×810×1260 | - | ||||||
Long run unit | 300×700×800 | 360×800×980 | ||||||||
Weight(kg) | Standard unit | 146 | 146 | 194 | 198 | - | ||||
Long run unit | 74 | 74 | 74 | 75 | 75 | 75 | 115 | 116 | 118 | |
General | ||||||||||
Noise at 1m dB(A) | <55dB (1 meter away) | <60dB (1 meter away) | ||||||||
Altitude | ≤1500; derate power by 1% per 100m between 1500m and 300m | |||||||||
Ventilation | Front to back standard | |||||||||
Protection level | IP20 | |||||||||
General and safety | EN62040-1/IEC62040-1 | |||||||||
EMC standars | EN62040-2 / IEC62040-2 | |||||||||
Method of specifying the performance and test | EN62040-3 / IEC62040-3 |