Overall efficiency up to 99.3% in intelligent ECO mode
Supports smart parallel function
Input current distortion (THDi) <3%
Input power factor >0.99
Eccellent generator adaptability
Widest input voltage & frequency range
Battery ground fault detection
Strong 0.9 output PF loading capacity
Key Features:
- Parameter
Nominal Power | 160KVA | 200KVA | 250KVA | 300KVA | 400KVA | 500KVA | 600KVA | 800KVA |
Input | ||||||||
Nominal input voltage | 380/400/415Vac, 3-phase 4-wire | |||||||
Input voltage range | 325 to 478Vac | |||||||
Nominal input frequency | 50/60Hz | |||||||
Input frequency range | 40-70Hz | |||||||
Input current distortion (THDi) | <3% | |||||||
Input power factor | ≥0.99 | |||||||
DC Feature | ||||||||
Number of battery blocks/string | 38 to 48 pcs ; default:40 pcs | |||||||
DC ripple voltage | <1% | |||||||
Output | ||||||||
Nominal output voltage | 380/400/415Vac, 3-phase 4-wire | |||||||
Output power factor | 0.9/1 | |||||||
Voltage regulation | <1 typical (Steady state); <5% typical value(Transient state) | |||||||
Transient response time | <20ms | |||||||
Phase voltage symmetry with balance load | +/- 1 degree | |||||||
Phase voltage symmetry with 100% unbalanced load | +/-1.5 degree | |||||||
THDv | <2% (100% linear load); <5% (100% nonlinear load) | |||||||
Bypass | ||||||||
Bypass input voltage | 380/400/415Vac, 3-phase 4-wire | |||||||
Bypass voltage range | -20% ~ +15%, other values settable through software | |||||||
Dimensions and weight | ||||||||
Depth x Height (mm) | 900x1000 x 1900 | 1200x1000 x 1900 | ||||||
Weight (kg) | ||||||||
System | ||||||||
Frequency precision (internal clock) | ±0.05% | |||||||
Online mode efficiency | Up to 96.5% | |||||||
System efficiency(in Intelligent ECO mode) | Up to 99.1% | |||||||
General | ||||||||
Operating temperature | ||||||||
Storage temperature | ||||||||
Relative Humidity | 0 ~ 95%, without condensation | |||||||
Max operation altitude | =1000m above sea level | |||||||
Noise (1m) | <74db | <76db | ||||||
IP degree oprtection | IP20 | |||||||
Standard | Compatible safety standard: C62040-1, Ul1778, IEC60950-1, IE Electromagnetic compatibility IEC62040-2, Design and test IEC62040-3 |